SLA Sealed Lead Acid Battery
The SLA, called sealed lead acid battery, which is one of lead acid batteries, is not subject to memory. Leaving the battery on float charge for a prolonged time does not cause damage. The battery’s charge retention is best among rechargeable batteries. Whereas the NiCd self-discharges approximately 40 percent of its stored energy in three months, the SLA self-discharges the same amount in one year. The SLA is relatively inexpensive to purchase but the operational costs can be more expensive than the NiCd if full cycles are required on a repetitive basis.
The SLA does not lend itself to fast charging — typical charge times are 8 to 16 hours. The SLA must always be stored in a charged state. Leaving the battery in a discharged condition causes sulfation, a condition that makes the battery difficult, if not impossible, to recharge. Unlike the NiCd, the SLA does not like deep cycling. A full discharge causes extra strain and each discharge/charge cycle robs the battery of a small amount of capacity. This loss is very small while the battery is in good operating condition, but becomes more acute once the performance drops below 80 percent of its nominal capacity. This wear-down characteristic also applies to other battery chemistries in varying degrees. To prevent the battery from being stressed through repetitive deep discharge, a larger SLA battery is recommended. Depending on the depth of discharge and operating temperature, the SLA provides 200 to 300 discharge/charge cycles. The primary reason for its relatively short cycle life is grid corrosion of the positive electrode, depletion of the active material and expansion of the positive plates. These changes are most prevalent at higher operating temperatures. Applying charge/discharge cycles does not prevent or reverse the trend.
There are some methods that improve the performance and prolong the life of the SLA. The optimum operating temperature for a VRLA battery is 25°C (77°F). As a rule of thumb, every 8°C (15°F) rise in temperature will cut the battery life in half. VRLA that would last for 10 years at 25°C would only be good for 5 years if operated at 33°C (95°F). The same battery would endure a little more than one year at a temperature of 42°C (107°F).
Engineers may argue that the word ‘sealed lead acid’ is a misnomer because no lead acid battery can be totally sealed. In essence, all are valve regulated.
The SLA (sealed lead acid battery) has a typical capacity range of 0.2Ah to 30Ah and powers portable and wheeled applications. Typical uses are personal UPS units for PC backup, small emergency lighting units, ventilators for health care patients and wheelchairs. Because of low cost, dependable service and minimal maintenance requirements, the SLA battery is the preferred choice for biomedical and health care instruments in hospitals and retirement homes.
Source: www.leoch.com